Selection and grounding requirements of lightning arrester

Release time:2026-05-29 00:00 Views:371 author:Xinlaida Security Technology Department source:technical knowledge
Explain the type, installation location and parameter selection of lightning arresters in the monitoring system, as well as the specific requirements for grounding resistance.

Lightning strike path of monitoring system

  1. Direct lightning strike: Directly hitting a pole or equipment has the greatest damage.
  2. Induction lightning: Thundercloud discharge induces surges on nearby lines and invades equipment along power lines and signal lines. This is the most common cause of damage.
  3. Ground potential counterattack: A nearby lightning strike causes the ground potential to rise and counterattack the equipment through the ground wire.

Surge protector (SPD) type and installation location

TypeInstallation locationFunction
Power supply lightning protector (level 1)Computer room main distribution boxDischarge large current
Power supply lightning protector (secondary/third level)Equipment box, cabinetFine protection equipment
Network signal lightning protectorCamera side + switch sideProtect network port and PoE
Two-in-one/three-in-one lightning protectorOutdoor equipment boxProtect power supply and network simultaneously
Video/PTZ lightning protectorAnalog system or dome camera control lineProtect coaxial and control signals

Key points for selection

  • Network lightning protector: Must support PoE (confirm support of af/at/bt and corresponding line sequence), Otherwise, abnormal power supply may occur.
  • Transmission rate matching: For Gigabit networks, you need to choose a Gigabit lightning protector. A 100 Mbit lightning protector will limit the speed.
  • Nominal discharge current In: General scenario ≥ 5kA (8/20μs), Areas prone to thunderstorms are more likely to be selected.
  • Limit voltage (Up): The lower the better, it should be lower than the withstand voltage level of the protected equipment.
  • Response time: Should be ≤ 25ns (nanoseconds).
  • Interface and protection level: Outdoor installation requires IP65 or above.

Grounding requirements

  • Ground resistance: General monitoring equipment room ≤ 4Ω; outdoor poles and equipment boxes ≤ 10Ω; areas with high soil resistivity can be relaxed and resistance reduction measures can be adopted.
  • Equipotential bonding:The equipment casing, metal brackets, poles, lightning arrester ground wires, and wire conduits must be connected together and grounded uniformly. Avoid potential differences.
  • Grounding wire: Sufficient cross-sectional area (generally ≥ 4mm², important areas ≥ 6mm²), Keep it as short and straight as possible and avoid loops (the inductive reactance under lightning current will significantly increase the residual voltage).
  • Independent grounding vs joint grounding: Priority is given to joint grounding (connected to the building lightning protection grounding network), When making a ground net alone, pay attention to the safe distance from other ground nets.

Maintenance

  • The lightning arrester has a deterioration indication window, which needs to be replaced when it turns red.
  • Inspection once a year before the thunderstorm season.
  • After the device is struck by lightning, even if it can still work, it is recommended to replace the lightning protection module.
  • Ground resistance is measured and recorded once a year.